Atomizing Train

Per NFPA, IRI & FM Standards


Click image to view full-size.

- - - - - Dashed lines indicate field installed piping and equipment.
______ Solid lines indicate factory installed piping and equipment.

1. Atomizing Media Flex Hose - 321 stainless steel construction, braided

2. Gauge Shutoff Valves - 1/4" N.P.T. needle valve

3. Pressure Gauge - Wika 4" dial, stainless steel case

4. Low Atomizing Pressure Switch - Mercoid, with visible set point indication

5. Gate Valve - Milwaukee, 300#, with replaceable gate

6. Check Valve - Milwaukee 300#

7. Atomizing Media Shutoff Valve - Gould, normally closed

8. Oil Impulse Line Shutoff Valve - 1/4" N.P.T. needle valve

9. Atomizing Media Differential Pressure Regulator

10. Low Atomizing Supply Pressure Switch - Mercoid, with visible set point indication

11. Strainer - Mueller, with 30 mesh screen

12. Steam Trap Shutoff Valve, - Milwaukee 300# gate valve, with replaceable gate

13. Steam Trap - Sarco, balanced pressure thermostatic steam trap

Optional Equipment

14. Check Valves - United, spring loaded

15. Oil Gun Purge Solenoid Valve - Gould, normally closed

16. Oil Gun Purge Pressure Regulator - Fisher

17. Oil Gun Purge Isolation Valve - Milwaukee, 300# gate valve, with replaceable gate

18. Pressure Relief Valve - Kunkle

19. Pressure Gauge - Wika 4" dial, stainless steel case

20. Gauge Shutoff Valve - 1/4" N.P.T. needle valve

21. Pressure Regulator Isolation Valves - Milwaukee 300# gate valve, with replaceable gate

22. Pressure Regulator - Fisher

23. Pressure Regulator Bypass Valve - Milwaukee 300# globe valve, with replaceable seat and disc

24. Check Valves - Milwaukee 300#

25. Gate Valves - Milwaukee 300#, with replaceable gate

Options

A1 = Oil Gun Purge System Items 14, 15, 16 & 17, factory installed. This system automatically cleans out the oil gun upon a "planned" oil burner shut down. When the burner control is turned off while firing oil, the unit is sent to low fire. The pilot is energized, the oil safety shutoff valves close, and the oil gun is cleaned out with atomizing media. The burner shuts down at the completion of this sequence. All the safety limits are monitored during this sequence. If a limit should fail, the sequence is stopped immediately, and all the fuel valves will close.

A2 = Atomizing Steam Pressure Reducing Station - If the atomizing steam supply pressure is over 200 psig, a pressure reducing station will be required. This option includes items 18, 19, 20, 21, 22 & 23, factory installed on the burner.

A3 = Atomizing Media Change Over Equipment - This includes items 24 and 25 shipped loose for field installation.

NEMA 4 - Changes items 3, 4, 10 & 19 to weatherproof (NEMA 4)

Specifications for Atomizing Media Train Piping & Fittings

Schedule 80 pipe with 300# malleable iron threaded fittings.

Supply Pressure

To inlet of atomizing train:
100-200 psig steam at 400 degrees Fahrenheit or less
100-200 psig compressed air
If the available atomizing media supply pressure is greater than 200 psig option A2 will be required.